This estimator shows how long a UPS keeps your NAS running in a power cut. It reads the runtime from the maker's own published runtime curve for that UPS at your load, with a new, fully charged battery, and checks it against the time your NAS needs to shut down safely.
Runtime falls much faster than load rises, so a battery capacity formula is not used. Pick your NAS (or enter its watts), add anything else plugged into the UPS, pick the UPS, and enter how long your NAS takes to shut down.
It covers 5 UPS models sold in Australia whose makers publish a runtime curve. For another model, use its maker's runtime chart.
1. What is on the UPS
2. How long the NAS needs
| Load | Runtime |
|---|
Choosing a UPS? The UPS Sizing Calculator checks every model against your load at once.
The maker's curve. UPS makers publish how long each model runs at different loads with a new, fully charged battery. For APC models NTK reads Schneider Electric's runtime calculator on the Australian product page at a set of loads; for CyberPower models it uses CyberPower's published runtime chart. Your load is placed on that curve: between two published loads the runtime is the straight line between them, the way the makers' charts join their points.
No figure outside the maker's data. Above the highest load the maker publishes, or above the UPS's watt rating, there is no runtime figure. Below the lowest load the maker publishes, NTK does not guess a number either: runtime falls as load rises on every published curve, so the page says runtime is longer than the maker's figure at its lowest load. That covers your need only as an inferred result, labelled as such, because the maker publishes no figure that low. Under 15 W of total load the page cannot tell at all: Schneider says APC Back-UPS models with No-load Shutdown turned on switch off while on battery when the attached load is less than 15 watts, describing a Back-UPS that shuts down after 15 minutes on battery with backup time still left. It applies only to Back-UPS models whose user guide mentions the feature. (APC (Schneider Electric), checked 2026-10-14). NTK does not know which models here have such a cutoff, so it applies to every model.
Your load is the NAS's watts plus everything else on the UPS. A picked NAS uses its maker's busy figure (Synology's Access, QNAP's Operating Mode, Typical and so on), measured under the maker's own conditions; a NAS sitting idle draws less, so its runtime is longer.
Runtime you need = the minutes on battery before the NAS starts shutting down + its shutdown time + any reserve. The verdict compares the two.
Battery age. The figures are for a new battery. No maker publishes a percentage for an older battery, so none is applied: an older battery gives less runtime than shown.
| Model | Rating | Output on battery | Outlets | USB data port | Maker's runtime (new battery) | Source |
|---|---|---|---|---|---|---|
| CyberPower UT650EG | 650 VA 360 W | simulated sine wave, line interactive | 3 Australian | No: None listed (no HID USB port, no management cable, no software) | 45 min at 50 W, 16 min at 90 W, 5 min at 180 W, 3 min at 200 W, 30 s at 360 W | CyberPower runtime chart, checked 2026-10-08 |
| APC Back-UPS BX750MI-AZ | 750 VA 410 W | stepped approximation to a sine wave, line interactive | 3 Australian (AS/NZS 3112) | Yes: USB data port (PowerChute Personal Edition) | 50 min at 41 W, 26 min at 80 W, 15 min at 125 W, 7.5 min at 200 W, 43 s at 410 W | Schneider Electric runtime calculator on the AU product page, checked 2026-10-08 |
| APC Back-UPS BX950MI-AZ | 950 VA 520 W | stepped approximation to a sine wave, line interactive | 4 Australian (AS/NZS 3112) | Yes: USB data port (PowerChute Personal Edition) | 47 min at 52 W, 28 min at 90 W, 12 min at 175 W, 5 min at 300 W, 28 s at 520 W | Schneider Electric runtime calculator on the AU product page, checked 2026-10-08 |
| CyberPower VP1000ELCD | 1000 VA 550 W | simulated sine wave, line interactive | 3 Australian | Yes: 1 HID compliant USB port, USB cable, PowerPanel Personal | 1 h 6 min at 60 W, 26 min at 137 W, 16 min at 200 W, 9 min at 275 W, 1 min at 550 W | CyberPower runtime chart, checked 2026-10-08 |
| APC Smart-UPS SMT1500IC | 1500 VA 1000 W | sine wave, line interactive | 8 IEC C13 (not Australian wall sockets) plus 2 IEC jumper cables | Yes: USB and serial ports, SmartConnect port (cloud monitoring) | 2 h 52 min at 100 W, 1 h 24 min at 200 W, 40 min at 350 W, 16 min at 600 W, 6.5 min at 1,000 W | Schneider Electric runtime calculator on the AU product page, checked 2026-10-08 |
| NAS (maker's figure) | UT650EG | BX750MI-AZ | BX950MI-AZ | VP1000ELCD | SMT1500IC |
|---|---|---|---|---|---|
| Synology DS225+, 16.98 W Access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| Synology DS425+, 28.25 W Access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| Synology DS925+, 37.91 W Access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| Synology DS1823xs+, 87.93 W Access | 16 min | 23 min | 28 min | 45 min | more than 2 h 52 min |
| Synology DS223j, 16.31 W Access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| QNAP TS-464, 40.536 W Operating Mode, Typical | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| QNAP TS-264, 29.086 W Operating Mode, Typical | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| QNAP TS-433, 22.54 W Operating Mode, Typical | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| QNAP TVS-H874, 96.247 W Operating Mode, Typical | 15 min | 21 min | 26 min | 41 min | more than 2 h 52 min |
| UGREEN DXP2800 GT, 42.36 W drive access | more than 45 min | 48 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| UGREEN DXP4800 GT, 42.36 W drive access | more than 45 min | 48 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| UGREEN DXP2800, 16.38 W drive access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| UGREEN DH4300 Plus, 22.89 W drive access | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| TerraMaster F4-424 Pro, 33.0 W read/write state | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
| ASUSTOR AS5402T, 22.9 W Operation | more than 45 min | more than 50 min | more than 47 min | more than 1 h 6 min | more than 2 h 52 min |
The NAS alone, with nothing else on the UPS. "More than" means the NAS draws less than the lowest load the maker publishes for that UPS, and the figure is the maker's runtime at that lowest load: an inferred result, not a published one. Under 15 W the table says "cannot tell".
Method last reviewed: 2026-10-14. UPS figures last checked at the makers' Australian sites: 2026-10-08.
Ask us anything about NAS, storage, or infrastructure. We reply by email.
Message sent!
We'll be in touch soon.